The Leoch LRCF12-170 is a 12 V front-terminal lead-carbon AGM monobloc rated at 170 Ah (C10) and
2.04 kWh per unit. LRC-series lead-carbon chemistry significantly extends cycle life beyond conventional
VRLA — approximately 4,000 cycles at 50% DoD and up to 8,800 cycles at 20% DoD — with a ≥12-year design
life per IEC 61427. The front-terminal M8 layout suits rack-mount telecom enclosures, UPS cabinets,
solar and wind storage systems, and container-based stationary installations.
03
Technical Specifications
Electrical
- Model
- LRCF12-170
- Chemistry
- Lead-Carbon AGM (VRLA)
- Format
- Front-terminal monobloc · 6-cell, 12 V
- Rated voltage
- 12 V
- Nominal capacity (C10)
- 170.0 Ah · at 1.80 V/cell
- Capacity (C3)
- 128.7 Ah · at 42.9 A / 1.80 V/cell
- Capacity (C1)
- 103.2 Ah · at 103.2 A / 1.75 V/cell
- Nominal energy (C10)
- 2.04 kWh
- Internal resistance
- ≈4.0 mΩ
- Cycle charge voltage
- 13.8–14.4 V · 2.30–2.40 V/cell
- Max charge current
- 51.0 A · at 25°C
- Max discharge current
- 85.0 A · at 25°C
- Self-discharge
- ≤3.5% / month · at 25°C
- Temp. coefficient
- −4 mV/cell/°C · −24 mV/°C (unit)
Cycle life (DoD)
- 20% DoD
- ~8,800 cycles
- 30% DoD
- ~6,400 cycles
- 50% DoD
- ~4,000 cycles
- 80% DoD
- ~1,600 cycles
Operating temperature
- Discharge range
- −20°C to +55°C
- Charge range
- −20°C to +40°C
- Storage range
- −20°C to +50°C
- Capacity at 0°C
- 86% of C10 nominal · ~146 Ah
- Capacity at 40°C
- 106% of C10 nominal · ~180 Ah
Dimensions
- Dimensions (L × W × H)
- 560 × 126 × 320 mm
- Weight
- 62.0 kg
- Terminal type
- M8
- Container material
- ABS · UL94V-0 flame retardant
Specifications are sourced from the manufacturer datasheet and believed accurate; they are provided for
informational purposes only and do not constitute a warranty. Availability is indicative and subject to